Customization: | Available |
---|---|
Certification: | ISO9001, CCC |
Protection: | Corrosion Resistance |
Still deciding? Get samples of US$ 67460/Set
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | Ore Box- RUISU-1200 Mining Enclosure |
|
Dimensions | Enclosure Length x Width x Height | 38.1 ft x 7.2 ft x 7.5 ft |
Number of installed mining rigs | 336 units with 3.25kW up to 4.0kW power consumption per rig |
|
Enclosure rating |
NEMA 3 / IP54 |
|
Power Power |
Power Input KW |
Upper Limit: 1,354 KW |
Input Voltage |
415VAC 3ph |
|
Inside Access |
3 phase power connection to inside access 4 Main Breakers |
|
Connection type |
3 Hot wires, 1 Neutral, 1 Ground, each phase Volts: 415VAC / 240VAC |
|
Distribution Panel and Breakers |
Each cabinet has 4 power distribution panel. Each distribution panel: 1 x 600A 3-pole molded case main circuit breaker, 4 x 175A 3-pole molded case circuit breaker, 84 x 20A 1P circuit breaker, 6x6A 3P circuit breaker, 1x10A 2P circuit breaker, 3x20A 2P circuit breaker, 1x32A 4P circuit breaker, 1xSPD 40 (3L+N) surge protector |
|
Power Distribution & Cabling |
1. Power distribution unit: main panel circuit breaker (Schnei der), distribution circuit breaker (Nader), contactor (Nader).
|
|
Cooling | Cooling technology |
Air Economizer with Evaporative cooling, 8 Panels per Container |
Industrial grade Exhaust Fans (550W per fan) |
16 Fans with automated louvers |
|
Airflflow (Cubic-Feet-per-Minute) |
376,000 CFM (638,828 Cubic Meter/Hour) |
|
Air filtering system |
Include air filter net and dust filter net | |
Additional technical details | Security | Key locks standard to dual entry/egress security doors |
Regulatory compliance | UL 489, Compliant to IEC 60950 and international wiring regulations |
|
External Environmental Operation limits | Operating temperatures | 40°F to 115°F |
Operating humidity range | 0 to 90% RH (below Condensation point) |
|
Operating altitude | 0 to 5,000 ft |